June 2019 - See this page for an updated solution.Bristol® 5457 ReplacementTo replace the Bristol® 5457 remote set point pneumatic controller, consider the Fairchild Models 24XF or 24XFM Motor Driven Precison Pressure Regulators and a Pneumatic Controller.The
Fairchild motor driven regulator provides
|
Sample Part
Number
(Part number for your application may be different.) |
Fairchild 24XFS1094003 |
Fairchild 24XFM1032N9R |
Key Features
|
*Lock in Last Position |
*Lock in Last Position High Accuracy High Pressures |
Input
|
4 - 20 mA | 4 - 20 mA |
Power Supply
|
12 - 24 VDC | 12 - 24 VDC |
Max. Supply
Pressure
|
500 psig | 500 psig |
Output Range
|
0.5 - 30 psig | 0 - 30 psig |
Exhaust
|
Tapped Exhaust with Constant Bleed | No Bleed |
Approvals
|
FM Explosion Proof | FM Explosion Proof Approval Pending Expected July 2012 |
*Lock in Last Position -
On loss of 4-20 mA signal there is a comparative
circuit which will fail in last position. In
addition, the DC motor will lock on loss of power.
|
|
|